Installation — Select Field Settings
Page 10
Factory Settings: The GasPoint is calibrated and tested before shipping. Prior to shipping they are factory set to
the commonly used values. To change the factory default settings see the applicable section:
The following settings are field selectable:
Dip Switch Overview
1. Calibration Time Delay: To set span, select a time delay of 30 seconds or 6 minutes. For remote calibration use
the 6 minute setting to allow time for the gas to reach the sensor. To save time and calibration gas,
GasPoint will begin the Span procedure when it senses the calibration gas.
Note: The factory default is 0.5 minutes (30 seconds). See Dipswitch 3 (CAL TIME) to change to 6 minutes.
2. Measuring Range: Select from up to four measuring ranges by setting Block 1 switch 4 and switch 5 to open or
closed. Both switch 4 and 5 are factory set to "open". See table below for selections
3. LOW and/or HIGH Relays: Select Non-latching or Latching. Factory default is set to open (non-latching).
4. LOW and/or HIGH Relays: Select De-energized or Energized. Factory default is set to open (de-energized).
Changing the Alarm and Calibration Gas Setpoints
5. Gas Alarms: Gas alarm levels are set to OSHA (Occupational Health and Safety of America) standards prior to
shipping. GasPoint is equipped with two alarm levels LOW and HIGH. To set, select (two, one or
none) alarm levels and set selected levels to any values desired. To change them see Setting Alarm
Setpoints. Factory defaults are listed below
6. Calibration Gas Concentration Level: To facilitate Auto Span, the calibration gas concentration expected is
preset. It can be changed at any time for the toxic and combustible gas Sensors. Set the standard
generally used in your facility. See Automatic Calibration Routine to change the value.
The Oxygen Sensor span is set to 20.9% and cannot be adjusted (For O2 calibrate in normal 20.%
ambient air or if the atmosphere may be deficient or enriched use Pure Air calibration gas.
Note 1: Calibration Gas Factory Default Values — It is recommended that the default values be changed if
selecting higher measuring ranges than the factory default measuring range. See page 13 and page
26 (Note 2).
Table 3: Factory Default Settings; Select Measuring Ranges
Gas Sensed
Units of
Measure
Select Measuring Range:
Alarm Setpoints
Calibration Gas
Factory
Default
O—O
Or Select
4. Closed
5. Open
Or Select
4. Open
5. Closed
Or Select
4. Closed
5. Closed
Factory Defaults
(Field Settable)
Factory Default
Value Level
Expected
Note1:
1
2 3 4
LOW HIGH
Combustibles 0-100% LEL % LEL
0 to 100
N/A N/A N/A
10% 20%
50% LEL
Hydrogen Sulfide ppm
0 to 100
0 to 50 0 to 500 0 to 20
10 ppm 15 ppm
20 ppm
Carbon Monoxide ppm
0 to 500
0 to 1000 0 to 100 0 to 50
35 ppm 200 ppm
200 ppm
Nitrogen Dioxide ppm
0 to 50.0
0 to 10.0 0 to 20 0 to 99.9
2.0 ppm 5.0 ppm
10.0 ppm
Hydrogen Cyanide ppm
0 to 20.0
0 to 50.0 0 to 100 N/A
4.7 ppm 10 ppm
15 ppm
Sulfur Dioxide ppm
0 to 100
0 to 50 0 to 20 0 to 10
2 ppm 5 ppm
20 ppm
Oxygen % by vol.
0 to 30.0%
N/A N/A N/A
19.5% 18.5%
20.9% Ambient
air or pure air
Ammonia ppm
0 to 50
0 to 100 0 to 500 0 to 999
25 ppm 50 ppm
50 ppm