Fault Alarm Conditions and Advice
In the event of a fault condition, the fault alarm will trigger activating any connected field interface. GasPoint will
advise which fault condition has occurred.
Under Fault Alarm conditions:
The non-latching fault relay be "on" de-energized during a fault condition.
The backlight will activate.
When the problem is corrected, GasPoint automatically returns to normal operation.
Fault Alarm Advice
Fault Condition
4-20 mA
Output
LCD Icons Displayed Display
SENSOR SELF-TEST FAIL
(The self-test has failed)
2.00 mA
Three (3) bars will flash on numeric display.
FAULT icon lights
ALARM icon flashes
"Sensor Fail" advice lights
Gas type monitored is constantly displayed
SENSOR FAULT
(no communications)
2.00 mA
Numeric display will read the last value (ppm/%)
present before sensor fault occurs
FAULT icon lights
ALARM icon flashes
"Sensor Fail" advice lights
Gas type monitored is constantly displayed
SENSOR DRIFT
2.00 mA
Numeric Display will read "00"
FAULT icon lights
ALARM icon flashes
“Sensor Error” advice lights and flashes
Gas type monitored is constantly displayed