Gas Alarm Conditions and Advice
If the current gas concentration meets or exceeds either alarm setpoint, the GasPoint gas alarm functions will
activate.
Note: If both or either gas alarm is turned OFF (set to zero or set to the same value) then no gas alarm condition
will exist for that alarm level.
The following alarm advice will activate in any gas alarm condition (LOW or HIGH):
The backlight will activate.
The 4-20 mA loop output will be normal (from 4 to 20 mA according to calibrated values)..
When the alarm condition no longer exists, GasPoint will exit alarm mode and enter normal operations.
Exception: If a relay is set to the latching position on either Low or High gas alarm, the relay will
remain “on” until the alarm is reset (ACKNOWLEDGED). Press the external button to reset the relay.
O2 (Oxygen) Note: (See Oxygen note 1 on page 13) An oxygen alarm level will depend on which
alarm setpoints have been set to Low and High. The
oxygen Low and/or High gas alarm setpoints are user
selectable for either enrichment and/or deficiency alarms as desired.
CAUTION: HIGH OFF-SCALE READINGS MAY INDICATE AN EXPLOSIVE CONCENTRATION.
Page 15
Gas Alarms Advice
Alarm Condition Alarm Relay LCD Icons Displayed Display
LOW GAS ALARM
If the current gas
concentration present
meets or exceeds the
low alarm setpoint.
*See O2 Note below
Low Alarm Relay triggers
field interface if the relay
is connected and a low
alarm setpoint is entered.
Numeric display will show the gas
currently present (ppm/%)
LOW icon lights
ALARM icon flashes
Gas type monitored is constantly
displayed
HIGH GAS ALARM
If the current gas
concentration present
meets or exceeds the
high alarm setpoint.
*See O2 Note below
High Alarm Relay triggers
a field interface if the
relay is connected and a
high alarm setpoint is
entered.
Numeric display will show the gas
currently present (ppm/%)
HIGH icon lights
ALARM icon flashes
Gas type monitored is constantly
displayed
OVER RANGE
(over level or over
range)
GAS CONDITION
If the gas concentration
present meets or
exceeds the full
measuring range.
OL icon lights
Gas type monitored is constantly
displayed
Note: If the alarms are turned OFF,
then no alarm icons will display
Vue de la page 18